Question
Answer
What strike do I specify with the 9975 device on a pair of 1 3/4" thick doors with a flat overlapping astragal mounting on the exterior of the active door?
Resolution:
Use the 575-2 strike with 9975 device on a pair of 1 3/4" thick doors with overlapping astragal mounting on the exterior of the active door. The strike lip has been cut off to eliminate any interfe...:
What strike is used for in-active leaf on pair of doors with 19-R?
Resolution:
The 571 strike is used on the in-active door leaf of a pair or on the 19-V door leaf when both doors are active per template.:
ACTIVE DOOR (IN A PAIR OF DOORS)
Resolution:
Door:
Are astragals required on 3 hour rated pairs of doors?
Resolution:
All 3 hour fire rated pairs of doors do require an astragal when used without a removable hardware mullion. Pairs of doors with removable hardware mullions are treated and listed as 2 single doors...:
Are flush bolts available on the inactive leaf of hurricane double doors with either FBC or NOA approvals?
Resolution:
Ives SB360 surface bolt at top and bottom are the only flush bolts approved for use on H-Series hurricane FBC or NOA applications? The only approved latching hardware for inactive leaf of pairs w...:
Can the bar style coordinators be used with swing clear hinges?
Resolution:
No, the geometry of a swing clear hinge prevents the coordinator from working correctly. The bar style coordinator will not hold the active door open far enough for the inactive door to clear the ...: