Can the SO12 or SO24 rectifier be used with 6000 series electric strike?

1. SO rectifiers are only recommended with fail secure electric strikes for momentary unlock.

2. SO12 requires 12VAC input +/- %10, and SO24 requires 24VACinput +/- %10.

3. The output of the SO kit (rectifier)  will measure more than 12VDC (or 24VDC)  when unloaded.  It is normal to read as much as 30 volts from the SO24 rectifier kit when it is not under load.  The voltage will drop when connected to load.