Category: Power Supplies

(Results from 21 to 30)
Can the 8200 power an EL panic device?
The 8200 can not supply the power needed on an EL dev ice. The EL device requires a Von Duprin PS914-2RS or PS914-4RL power supply or the older Von Duprin PS873-2 or PS873-4TD models....
Power Supplies » Standard » PS900 Series » Von Duprin
Where are the Data sheets or Installation Instructions for the 900 series Power Supplies?
Data sheets and installation instructions for 900 series power supplies are available at http://us.allegion.com/Services/TechSupport/Pages/home.aspx?ps=Electronic%20Security&pc=Electronic%20L...
Power Supplies » Standard » PS900 Series » Von Duprin
Why is the Von Duprin PS873 power supply buzzing or chattering?
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the output...
Power Supplies » Standard » PS900 Series » Von Duprin
Why is the EL wiring adaptor now required when using the new PS900 power supplies?
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor. The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or 900-4RL...
Power Supplies » Standard » PS900 Series » Von Duprin
If using the alarm kit-ALK with the 99 device what power supply is needed?
Exit alarm ALK operates with 9VDC battery and doesn't required a power supply.If you choose to hard wire the exit alarm ALK use the PS902 power supply.Exit alarm ALK requires 24VDC regulated power sup...
Power Supplies » Standard » PS900 Series » Von Duprin
What took the place of the Von Duprin 873-DE option board?
We no longer offer a delay egress board in the P900 series power supplies.The delay egress is controlled in the exit device (Von Duprin Chexit), the magnetic lock, or other locking device....
Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin
What do I need to use a fire alarm board with a PS914?
 The Basic PS914 power supply will not accept a 900-FA fire alarm board. 900-8F option board is required with PS914 power supply to accept 900-FA fire alarm board (900-8F is an adaptor board for 9...
Power Supplies » Standard » PS900 Series » Von Duprin
How long will the battery back up work for on the PS914-900BBK?
Attached table provides how long the battery back up will last with a PS914 power supply. Load (Amp DC) Battery backup time Comments 0.3 Amp 20 hours Continuous load ...
Power Supplies » Standard » PS900 Series » Von Duprin
What power supply replaces the PS 873 - 4TD?
The standard Von Duprin PS873 power supply was replaced by the PS914 power supply.NOTE: The newer PS900 option cards can NOT be used in the PS873 power supplies. The PS873 option cards also can N...
Power Supplies » Standard » PS900 Series » Von Duprin
What is the purpose of the 900-2RS board?
The 900-2RS option board is used with PS914 power supply to isolate the inputs such as key pads or card readers from the outputs for EL electric exit devices.  The EL draws 16 amp inrush that needs t...