Can a PS902 Power Supply damage an Schlage MTK15 Reader?
                                Yes - the PS902 MUST be strapped for 12vdc operation when powering a Schlage reader. &n...
Schlage Commercial » Power Supplies
Should I use a 12 or 24v power supply for the CT5000
While the CT5000 can take either you must use a 12 volt  fully regulated and filtered power supply  should be used, due to the credential reader power requirements range from 5 to 16 vo...
Schlage Commercial » Power Supplies
What would cause 900-2RS not to provide voltage on O2 for double door application?
There is a jumper on 900-2RS that is field selectable for individual or sequential mode.If jumper is set for individual, input I1 will activate output O1and I2 will activate output O2.If jumper i...
Schlage Commercial » Power Supplies
What power supply is required for the QEL device?
For a simple application with a card reader and 1or 2 QEL devices, a PS902 x 900-2RS is required. The QEL device has a 1 amp inrush of 24VDC to retract the exit device latch, and t...
Schlage Commercial » Power Supplies
Can you run 24volts thru the NO and C of the 900-FA board?
Yes, 24VDC is fine, since the relay on the FA board is rated for 30VDC 1A max....
Schlage Commercial » Power Supplies
What does LGR indicate for PS902 2RS LGR?
LGR refers to the finish of the power supply, light grey....
Schlage Commercial » Power Supplies
What are the details about 900-KL, 900 series power supply locks?
Cam locks for the 900 series (902/904/906/914) power supplies can be ordered with the power supply or as a separate item.  The model number for the lock is 900-KL, and the part number is 44486850...
Schlage Commercial » Power Supplies | Schlage Commercial
Can I change voltage on a 6000 series strike in the field?
Yes.For a 6100 or 6200 series strike,  you can order a strike from the Von Duprin price book .  Then, the strike can be replaced in the field.For assistance,  please contact support at ...
Schlage Commercial » Power Supplies
What power supply is required for a Von Duprin electric strike?
The current Von Duprin power supplies for electric strikes  are PS902, PS904,  and PS906.The specific supply needed will be determined by the overall current requirements of the strikes (and...
Schlage Commercial » Power Supplies
Will the PS873-2 power supply still operate the Von Duprin QEL exit device?
Yes.  Given this power supply was discontinued around 2010,  verify the output voltage still measures near 24VDC.If the power supply is not operating as expected,  please contact V...