wiring for cx

RELATED FAQS

Question
Answer
The EL Wiring Adapter is not needed for a CX device.
The part number for "CX Wiring Assembly" also called "Ten Wire Connector" is 112018-00.
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
The hole should be drilled in the field once the end cap is located on the door.  It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the Green an...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
Chexit devices shipped after 8-24-2015 with motor driven has a twelve wire connector wires and is keyed and can only plugged into the Chexit module in one direction.Chexit devices shipped...