Wiring Diagram for electric strike and maglock

RELATED FAQS

Question
Answer
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
Partner Solution: Integrated Access Control Solution with AD-300 Hardwired, AD-400 Wireless Locks and Avigilon RedCloud Access Control System.See the download cut sheet at:Avigilon Red Cloud&n...
The wires on 6000 series electric strike solenoid are non polarized.
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below.  Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 12VDC -...
Wiring and Riser diagrams can be accessed at:Common wiring diagrams can be accessed at:  http://kc.allegion.com/.   Click on the "Common Wiring Diagram" link.To request a custom wiri...
 The 10-042 is an electric strike used for cylindrical and tubular latch sets.  VOLTAGE  24 VAC  12 VDC  AMPERAGE  0.74A 0.33A   FREQUENCY  60 HZ ...
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable. To power the 24VDC electric strike or maglock off a LCN Se...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
Applies to L9090EL/EU, L9091EL/EU, L9092EL/EU, L9093EL/EU, L9094EL/EU, L9095EL/EUThe Schlage electrified L-Series wiring diagram can be found here and the re...
Applies to L9080EL/EU. L9082EL/EU (Discontinued)The Schlage electrified L-Series wiring diagram can be found here and the requirements are listed below. 24VAC or 24VDC (maximum 26V, ...
Click here to show the differences of an installed lockcase between the L9090, L9091, L9092, L9093, L9094, L9095 EL/EU and the L9080 EL/EU
The MA lock can be specified in a 12 or 24V DC configuration (default is 12V). Additionally, an AC power source may be used as long as a rectifier is installed in the circuit (not provided). He...
For additional details and a wiring diagram see the MA service manual page on electrical requirements here. 
As of June 2011 the electrified T locks can support 12 or 24 Volts.  You do not need to specify 12 or 24 when ordering since the solenoid is capable of either voltage out of the...
Prior to June 2011 the T lock only supported 24V and the electrical requirements were as follows: 0.185 amp @ 24VDC Wire Gage 22 AWG See wiring diagram here - (Previous 2 wire versi...