Question
Answer
What would make the PS914-2RS cycle on and off?
Resolution:
The following could cause the PS914-2RS Power Supply to cycle on and off: The wrong wire gauge or run distance from power supply to the EL device. Click HERE for wiring requirementsOverlo...:
What is the maximum distance you can wire a PIB300 or PIB301 from a Access Control Panel?
Resolution:
See the User Guide instructions in the links below:
What are the wire gauge and length requirements for QEL devices?
Resolution:
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...:
How do you route the wires for an E996L trim through the exit device?
Resolution:
The wires run through the device out to the EPT. See step 7 on page 5 of E996L instructions.:
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
What size wire and run is recommended when using a PS914-2RS?
Resolution:
For Product Shipped Prior to August 2012 using the old (black) potted module:a. 0-100 ft 14 gauge wireb. 0-200 ft 12 gauge wire&nbs...: