what PS for cx

RELATED FAQS

Question
Answer
The EL Wiring Adapter is not needed for a CX device.
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
Chexit devices shipped after 8-24-2015 with motor driven:You can power up to four Chexit devices per PS914 power supply. 0-200' run wire, use #18 gauge.0-500' run wire, use # 14 gauge.
Chexit devices shipped prior to 8-24-2015 with solenoid driven:You can power up to four Chexit devices per PS914 power supply on low traffic doors.0-100' run wire, use #14 gauge.0-200' run wire, us...
Following information determine number of the Chexit devices that were shipped prior to 8-24-2015 from the factory with solenoid driven can be hooked up to a single Von Duprin PS873 or PS914 p...
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
The hole should be drilled in the field once the end cap is located on the door.  It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...
Schlage Electronics 1910 series horn can be used as an external horn with Von Duprin Chexit device.