what LCN operators have fire alarm contacts
”
RELATED FAQS
Question
Answer
Why does the PS900 power supply not provide any DC output when AC power light is on?
Resolution:
The following items may cause the PS900 series power supply to have no DC output voltage. 1. If the DC voltage selection jumper is missing, the power supply will not provide any D...:
What power supply do I need for my 2 QELA devices with LCN auto operator?
Resolution:
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...:
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
Von Duprin Chexit device keeps going into alarm by itself.
Resolution:
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...:
How are actuators wired to a 7900 or 7980 series control box?
Resolution:
The "common" of all the actuator switches will connect to terminal 10. The N.O. (normally open contact) will connect to Terminal 5, 6, 7 or 8 depending on which control box is used and the function...:
Does the 4600 series operator have a Push N Go feature?
Resolution:
The 4600 Series operator does not have a Push N Go feature. The LCN operators with a Push N Go feature are the Senior Swing, Benchmark, and the Falcon 8200 series.:
Can a magnet, or sentronic device, be released and close the door from a button at a desk?
Resolution:
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiri...:
Does LCN have a closer or operator for sliding doors?
Resolution:
LCN does not offer any products for sliding doors.:
What do I need to use a fire alarm board with a PS914?
Resolution:
The Basic PS914 power supply will not accept a 900-FA fire alarm board. 900-8F option board is required with PS914 power supply to accept 900-FA fire alarm board (900-8F is an adaptor board for...:
Is the 3130 Series closer Fire Rated?
Resolution:
The 3130 Series closer is UL listed- Fire Rated (UL-10C) for up to 3 Hr. The Door and Frame Manufacturer needs to be contacted to verify their Door/Frame rating would not be ...:
How do you get a 4600 Series operator out of "Fire Alarm" mode?
Resolution:
The "Fire Alarm" indication occurs when there is no connection across terminals 13 & 14. Check to verify that the "Fire Alarm" shunt (R1 jumper) on the I/O board has not been cut. Install jumpe...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
What are the amperage and power supply requirements for the Von Duprin Chexit (CX) devices?
Resolution:
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...:
How do I get service on my Astro Swing operator that isn't working properly?
Resolution:
LCN does not does not have or supply any information for the old (obsolete) "High Energy" Dor-O-Matic Sliding doors, Bi-Fold doors or Astro Swing doors. You MUST be AAADM certified to work on, or g...:
Is there a way to get a dry contact signal from a Chexit device when it is in alarm?
Resolution:
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red) of the harness connector cable tha...:
Do all Senior Swing operators come with the Push-N-Go feature?
Resolution:
All Senior Swing models are heavy duty operators and have the Push-N-Go (PNG) feature. This feature is a programmable function in the control module. The PNG settings are:&nb...:
What is required to be ordered with the Chexit?
Resolution:
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required&nbs...:
What LCN operator would be equal to Horton 4000 series operator?
Resolution:
The Senior Swing series operator would be the LCN equivalent to the Horton 4000 series operator.:
Where are hardware templates?
Resolution:
All the templates can be found at us.allegion.com Please click here :
What is needed to keep the EL device retracted all day?
Resolution:
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...:
What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.: