what is hi low on door properties in sus

RELATED FAQS

Question
Answer
The coin cell Nuisance Delay on CO200 and CO250 can be temporarily disabled using the Schlage Utility Software.
Once disabled via the SUS application, the CO lock will no longer delay the access for valid credentials.
If your CO lock began indicating a low coin cell (Nuisance Delay) after a door file has been downloaded, the coin cell is low and should be replaced. (CR2032)The coin cell Nuisance Delay will be "A...
The coin cell Nuisance Delay settings in the SUS application is not available until such time that a Door file is successfully downloaded to the lockset.
The coin cell is ignored when the lock sets are used with Manual Programming ONLY or while in Construction mode.
The SUS can change the logic polarity of the AD400/WRI400 PIM400-TD2 outputs RTX, DPS, TROUBLE, and REN from LOCK/DOOR PROPERTIES Edit tab. You can change High to Low to High using the ed...
  These SUS settings have no effect when the AD400 is linked to a PIM400-485; because the PIM400-485 reports the logic status with RSI-485 commands and not logic levels. The settings are gray...
-On the AD series offline locks only you can change the lock function from Classroom/Storeroom to a Privacy, office or apartment function out in the field. - This is done via the HHD/SUS using...
The 2030 closer requires a minimum 1-3/8" top rail on the door for the standard track.  For a top rail less than 1-3/8" and as narrow as 1", you could use the l...
The 4630/4640 Series operator is designed/recommended for a door that will see mostly manual traffic with the occasion automatic/ handicap operation.
With the SUS connected to the AD400, in the EDIT tab there are radio communication settings "FIRST/DELAY/RETRY." FIRST - Is the first delay after the initial transmission of credential data, befor...
AD400 factory default settings when shipped are FIRST = 300 (m sec), DELAY = 200 (m sec) and RETRY = 5  
To change FIRST/DELAY/RETRY connect and couple the SUS/HHD to the AD400 and find under the EDIT tab the FIRST/DELAY/RETRY settings. See notes Or connect the SUS/HHD t...
Dynamic Channel Switching is a feature of the Schlage AD-series wireless access point modules. Dynamic Channel Switching (DCS) increases the robustness of the wireless RF communication in a noisy r...
  Here is a Technical Note on what Dynamic Channel Switching is, what it improves, how to set-up, and frequently asked DCS questions. DCS Tech Note here  
Setting Dynamic Channel Switching   1)     Connect and couple the SUS to the PIM400 you intend to change. See the SUS User Guide for details   2)     Under “PIM Properties” and the “Edit” tab is ...
Intumescent seals or gaskets are not required on fire rated steel doors. Generally speaking, the requirement for intumescent seals or gaskets are a function of the individual manufacturers’ listi...