voltage electric strike

RELATED FAQS

Question
Answer
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below.  Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 12VDC -...
For all models of 6000 series electric strike, except the 6300 & 6400, the color of the solenoid wires determine the voltage.  Black wires are used on 24VDC solenoids and yellow wir...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
Follow the steps below to troubleshoot the problem. Measure the voltage at the electric strike. If the strike is FSE and not locking there should be no voltage at the strike and if it is FS there ...
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid.  You must change to a 24V solenoid, part number 050240-00.