vertical rod exit device with flush bolts

RELATED FAQS

Question
Answer
You should use the LX switch with the Von Duprin surface vertical rod exit device because the rods are exposed and are vulnerable to attack. IE, the top rod can be grasped and forced down to retrac...
Hardware falling off a door is caused by one or all of the following issues: Field abuse Improper internal reinforcements in the door Improper field preparation The top or bottom rod case can...
The 98/99 rim and vertical rod exit devices are shipped with NL drive screw to function as a Night Latch. To convert the device to Class Room, remove the NL Drive Screw on 98/99 center case ass...
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...
To convert the Von Duprin 98/99 Rim or Vertical (Rod or Cable) Exit Device with functional lever (996L-R/V) to act like a rigid lever (996L-NL-R/V) with key over ride follow these steps: Remove ...
The AD or CO - 993 is NOT compatible with a Von Duprin 98/99 Concealed Vertical Rod exit device on wood doors.