The 4110 series closer is installed on a flush transom frame using the -419 flush panel adapter.
Steel transom panels are available: 1 3/4" thick panels - supplied in L-Series (L20, L18 or L16-Series) laminated construction. Recommended down sizing is as follows: Without Transom Bar 3...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.  NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...
Side Light and Side Panel frames - Side Light and Side Panel frames are not KD (Knock Down), they must be assembled and welded. All side lite and side panel frames must be assembled and welde...
Steelcraft doors and/or frames do not contain any asbestos. Steelcraft did use asbestos in the following products: Steelcraft S16-Series stile and rail door with flush panel and UL fire door l...
Types of astragal offered from Steelcraft are as follows: "Z" Astragal - For information on "Z" astragal types and attachment refer to the TD Manual page 3.3.17. Most commonly used on double ...
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...