Question
Answer
What is the maximum frame size for a label transom and sidelight frame?
Resolution:
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes).In masonry wall application the maximum is 13'6" x 12'2"In stud wall application the maxi...:
How do you install a 4110 with flush transom frame?
Resolution:
The 4110 series closer is installed on a flush transom frame using the -419 flush panel adapter.:
Can decorative metal panels be installed over the entire surface of fire doors?
Resolution:
Decorative metal panels can only be attached if the panel manufacturer is UL listed in UL’s category GVUZ. All installation, sizes and hourly ratings are in accordance with that manufacturers” ...:
When using a 9927 and you have a flush transom above is there a bracket to mount the latches to?
Resolution:
When using 98/9927 with flush transom above: You will need to use a 260U strike for flush transom applications OR a 260U-F strike for 98/9927-F fire rated device.:
Can louvers be installed in fire rated transom frames?
Resolution:
NO - Louvers are not approved for installation in a fire rated transom / side panel frames. NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...:
Can a 1 3/4" thick panel be used in a fire rated transom frame with a transom bar?
Resolution:
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...:
What is the standard undersize for Steelcraft transom panels?
Resolution:
Steel transom panels are available: 1 3/4" thick panels - supplied in L-Series (L20, L18 or L16-Series) laminated construction. Recommended down sizing is as follows: Without Transom Bar 3...:
Does Steelcraft offer a KD (knocked down) assembly for sidelight frames?
Resolution:
Side Light and Side Panel frames - Side Light and Side Panel frames are not KD (Knock Down), they must be assembled and welded. All side lite and side panel frames must be assembled and welde...: