schlage lever droop

RELATED FAQS

Question
Answer
Issue: One or both levers don't stay horizontal and droop down.Facts: Falcon T series locks in a high use application.Cause: Weak or broken springs within the springcage.Solution: Replacement sprin...
Levers may sag due to an incorrectly installed springcage or an incorrect springcage.Mortise locks with a fixed (rigid) lever such as an L9080 will use a spacer on the rigid lever (outside) and a s...
The spring in the hinge case or end case assembly lifts the crossbar and both lever arms.  If broken, the crossbar and lever arms will drop down. The weight of the crossbar and levers will automati...
ND-series locks manufactured on or after January 30, 2017 will ship with an improved spring cage and matching lever design. The design features are noted below. Because of this change, there a...
NOTE: ND locks manufactured on or after January 30, 2017 will no longer make use of the soft durometer spacer. The improved spring cage and matching lever eliminates the need for this spacer.Schlag...
You can order an L lock with a lever on one side and knob on the other as long as it's still rose by rose, or escutcheon by escutcheon (must be same style escutcheon). EXCEPTIONS: Knob trim on the...
Includes the SL1 lever on one side and the SK1 knob trim on the other side.
Falcon D series deadbolts will not accept Schlage Key-in-lever cylinders. The faceplate plug hole is smaller in diameter than the Schlage plug and does not fit flush when i...
For a Schlage "C"  keyway:  Specify "CP6" as the cylinder suffix when ordering  D100 or D200 locks (All other Schlage keyways are not available).
This change was implemented in firmware package CO.A.6 (or later) to help the customer in the communication and coupling process between the CO200 (CO250) and the hand held device (HHD). ...
The green LED is to be lit up until the spindle (Triangles and Key Switch) are aligned properly; providing a visual indication of the problem.  
If the mechanical alignment of the triangles on the back of the outside escutcheon are not aligned, the CO200 or CO250 will not connect with the SUS/HHD and will appear to be unresponsive...
In firmware CO.A.6 (or later) the Schlage button on the CO200 (CO250) will turn green anytime that the spindle triangles on the front escutcheon are out of alignment or the mechanical key switch is...
When unlocking the CO200 door by mechanical key override, the green led will be continuously ON until the key is released. This will occur after firmware CO.A.6 (or later) has been installed int...