Can protective plates be attached to fire rated door?
Resolution:
Yes, Steelcraft doors we are approved up to 48" in height or not to exceed a total 2304 square inches per face. Protective plates are usually flat sheets of metal or plastic applied to one or both...:
Is the Von Duprin Guard-X exit device fire rated?
Resolution:
The Von Duprin Guard-X exit device is not fire rated because the deadbolt is not spring loaded. Therefore, there would be no positive latching as required on a fire rated opening. :
Is the 2670 Guard X fire rated?
Resolution:
The Von Duprin 2670 Guard X is used only on non fire rated doors thus is not fire rated.:
Can a filler or cover plate be used to blank out a EPT prep on a fire rated frame?
Resolution:
Yes, a filler plate can be used to cover an EPT prep as long as it is made from the same material as the frame. This information can also be found in NFPA 80 under Chapter 5 for Field Modifications.:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...: