PANIC HARDWARE REQUIRED AT DOUBLE DOORS

RELATED FAQS

Question
Answer
The use of Panic Hardware and/or Fire Exit Hardware is required by the International Building Code (IBC) and NFPA 101 – The Life Safety Code, depending on which code and which edition of the code i...
Panic Hardware and Fire Exit Hardware are two different types of exit devices, and the proper selection is determined by code requirements. Panic Hardware is an exit device which is tested for u...
The most obvious difference (in the device) is the lack of mechanical dogging on a Fire Rated Device.  There are some internal parts that may be different and the method it is secured to the d...
Panic devices are not design for exterior application. As with any mechanical device, exposure to the elements may affect the operation and life of the device and/or finish and may void&nbs...
Water and electricity do not mix.  Von Duprin electrified devices can NOT be used in an exterior environment.
The Special Von Duprin 2' door device as of 02-07-14 is now shipped with UL Panic Hardware label or UL Fire Exit Hardware label.  The 2’ devices are most commonly used in 5...
The 4170 cover plate can be used to cover the 86 & 161 prepped doors.
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
Allegion does provides professional support to Architects and Design Professionals. For information related to specification development and support, Website for Architects and Design Professiona...
Allegion provides professional access control support to Security Consultants and Security Integrators.  For information related to specification development and support,Access Contro...