paladin frame installation
”
RELATED FAQS
Question
Answer
What hinges can be used on tornado doors?
Resolution:
The following hinges are available on Paladin series doors and frames: Butt hinges - 4 1/2" or 5" ball bearing type either standard or heavy duty Continuous hinges - full ...:
What is the backset for the Von Duprin WS9827 device when installed on Steelcraft Paladin series door?
Resolution:
The backset is 2 3/4" from edge of door to the center line of the device and strike. The preparation for the WS98/99 strike must be specified when placing order for the frame. :
Can out of square frames be adjusted?
Resolution:
It is the responsibility of the installing contractor to install all material in accordance with SDI or HMMA installation standards and tolerances. Out of square frames which are installed out...:
Can Steelcraft doors be prepped for the 98/9949 Concealed Vertical Cable Exit Device?
Resolution:
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device.L, B, CE, T and CE-Series doors are available factory preparedDoor prepa...:
Can out of plumb (twisted) frames be adjusted?
Resolution:
Out of plumb (also referred to as twisted) frames usually cannot be adjusted."Out of Plumb or Twisted frames (or jambs)" is a condition created by improper wall construction and/or improper in...:
What is the rough opening in walls for frame installations?
Resolution:
For DW, K three sided frames and four sided borrowed light frames: Three sided frame = door opening width (order size) plus 1 1/2" minimum to 2" maximum and the door opening hei...:
Does Steelcraft have frame installation instructions?
Resolution:
It is always recommended to point installers to the industry installation manuals which are very comprehensive and are ANSI documentsClick here to get the updated link to the Steelcraft Shop M...:
Can a filler or cover plate be used to blank out a EPT prep on a fire rated frame?
Resolution:
Yes, a filler plate can be used to cover an EPT prep as long as it is made from the same material as the frame. This information can also be found in NFPA 80 under Chapter 5 for Field Modifications.:
What are the installation tolerances for hollow metal frames?
Resolution:
Industry standards for hollow metal frames installation tolerances have been developed by both the SDI (Steel Door Institute) and HMMA (Hollow Metal Manufacturers). Both standards are based on th...: