operators with maglocks

RELATED FAQS

Question
Answer
If a 4600 clicks, but won't open the door: Verify proper connection of all the control box connectors. Verify correct manual operation of door. Verify actuator connections and any strike/maglo...
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.
If the Main AC fuse is blowing, the control box is defective and needs to be replaced.  The "Main Fuse" is a (5x20MM) 1 Amp Slow Blow fuse. If the 12VAC fuse is blowing, verify they are not trying...
INPUT -- 120 volts AC @ 1 amp. OUTPUT -- 12 volts AC @ 0.25 amp (1/4 amp).
The Falcon 8200 series operator requires a input of 120 VAC @ 1 Amp.
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable. To power the 24VDC electric strike or maglock off a LCN Se...
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...
Yes, the 4600 Series operators have a built in ES (electric strike) relay that can be used to unlock a strike, maglock, or EL device before opening the door.