What would cause a 4600 Series operator to open up and intermittently stick open?
Resolution:
If manually it opens and closes fine, check to make sure one of the actuators is not getting stuck in the on position. Verify that the "Operating Indicator" LED's -- "POWER and SAFETY CLEAR" LED's ...:
Why would a Falcon 8200 operator have an inconsistent opening?
Resolution:
An inconsistent opening is normally caused by the arm not being installed correctly. The arm must be installed while the operator gearbox is in the full open position, and the door at 90° open posi...:
What causes a Senior Swing door to hang open and not close?
Resolution:
First, turn off the power to the Senior Swing. If the door closes, check controller for a constant activation signal from an activation device. If door continues to hang up and will not close...:
What would cause a 4600 operator to click a few times when the actuator is pushed, but not open the door?
Resolution:
If a 4600 clicks, but won't open the door: Verify proper connection of all the control box connectors. Verify correct manual operation of door. Verify actuator connections and any strike/maglo...:
What would cause a Senior Swing to open too far?
Resolution:
The Senior Swing operator is designed to power open the door to 90°. The built in dead stop (in the gearbox) prevents it from opening any further. If the Senior Swing operator is opening to far (pa...:
Why does the auto operator not open the door when installed with a Chexit?
Resolution:
Chexits are NOT electric latch retraction devices, therefore the latch will not retract and allow the opener to swing the door open. Chexits block and unblock the latch. In order for a Ch...:
What could cause a 9100 Series Benchmark operator not to open when the actuator is pushed?
Resolution:
If the 9100 Series Benchmark operator does not open when the actuator is pushed: Verify the unit has 120 volts applied to it. Verify the the power light on the control box is on. If not, check ...:
What would cause my 4600 (4630/4640) Series operator to keep trying to open and squeal after opening to 90 degrees?
Resolution:
"Opening Force" adjustment could be set to strong (high). This adjustment is a turn pot adjustment which can be found on the controller. Try adjusti...: