operators open but wont close

RELATED FAQS

Question
Answer
If manually it opens and closes fine, check to make sure one of the actuators is not getting stuck in the on position. Verify that the "Operating Indicator" LED's -- "POWER and SAFETY CLEAR" LED's ...
An inconsistent opening is normally caused by the arm not being installed correctly. The arm must be installed while the operator gearbox is in the full open position, and the door at 90° open posi...
First, turn off the power to the Senior Swing. If the door closes, check controller for a constant activation signal from an activation device. If door continues to hang up and will not close...
If a 4600 clicks, but won't open the door: Verify proper connection of all the control box connectors. Verify correct manual operation of door. Verify actuator connections and any strike/maglo...
The Senior Swing operator is designed to power open the door to 90°. The built in dead stop (in the gearbox) prevents it from opening any further. If the Senior Swing operator is opening to far (pa...
Chexit devices are NOT electric latch retraction.  In order for Chexit device to operate with an auto operator you will need to add a rim electric strike on a single door or a pair o...
If the 9100 Series Benchmark operator does not open when the actuator is pushed: Verify the unit has 120 volts applied to it. Verify the the power light on the control box is on. If not, check ...
       "Opening Force" adjustment could be set to strong (high).  This adjustment is a turn pot adjustment which can be found on the controller.  Try adjusti...