NO HORN CHEXIT BORD

RELATED FAQS

Question
Answer
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
Chexit devices are NOT electric latch retraction.  In order for Chexit device to operate with an auto operator you will need to add a rim electric strike on a single door or a pair o...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
A thumbpiece, knob or lever trim left in the unlock position would be locked when the Chexit is armed and unlock when the Chexit device is disarmed. To keep the outside trim in the lock p...
For Chexit devices with solenoid driven shipped from the factory prior to 8-24-2015, the RX switch is ordered as a "Special CX RX Switch".  It may only be installed or adjusted on ex...
There is no conversion kit for Von Duprin Chexit device.  If delayed egress Chexit device is required, the entire device must be replaced.
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
Chexit devices shipped after 8-24-2015 with motor driven: The Chexit device will use a 1 1/4" mortise cylinder with straight cam. Schlage cylinder 20-001-114 recommended. CAUTION: The length of t...
Chexit devices shipped prior to 8-24-2015:The CX device will need a 1 1/4" mortise cylinder with a straight cam per page 2 of the installation instructions. A 996L-M for a 1 3/4...
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
Schlage Electronics 1910 series horn can be used as an external horn with Von Duprin Chexit device.
If the horn fail to operate in the CX device you need to replace the Chexit module. 040086 is the part number for devices shipped after 8-24-2015 with motor driven.050228 is the...
Followings are the reason for 98/99 exit alarm ALK not sound when push bar is activated. Make sure key switch on exit alarm ALK is turned on, wait for 20 seconds before you activating the pushba...
Replacing the battery on the 2670 should not cause the unit stop working. Make sure the spring that provides tension on the plastic finger is not bent out. The spring should be at a 90 degrees...
See PCB replacement instructions below. The horn is part of the board and can only be replaced by replacing the entire board.
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...