ives automatic flush bolt fire
”
RELATED FAQS
Question
Answer
Are flush bolts available on the inactive leaf of hurricane double doors with either FBC or NOA approvals?
Resolution:
Ives SB360 surface bolt at top and bottom are the only flush bolts approved for use on H-Series hurricane FBC or NOA applications? The only approved latching hardware for inactive leaf of pairs w...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
Does Ives offer a 296G Flush Bolt?
Resolution:
The 296G is is not a model number but rather the UL listing number. This listing would be on many Ives Flush Bolts including; FB30 and FB40 series Automatic Flush Bolts FB50 and FB60 ...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
What is the part number for the former F588 from Monarch?
Resolution:
The top latch for a Fire rated surface vertical rod device is part #650375-00 which replaced the old part #F588.:
Where do I install my Auxiliary Fire Latch (AFL) in a Less Bottom Rod, Fire Rated (LBR-F) exit device?
Resolution:
Installation should be 6" from bottom of the door. See attached templates as reference. T-5494 for HM Doors W-5494 for Wood Doors:
At what degree will the AFL (Auxiliary Fire Latch) bolt release?
Resolution:
1400 degrees which is approximately 20 minutes after the fire starts.:
Does Von Duprin have a fire latch that will go into the floor?
Resolution:
Auxiliary fire latch is tested only from door to door latching by Von Duprin. Some door manufacturers have tested our devices LBR and use additional fire latches to pass the fire test. Contact the ...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
What is the difference between Panic Hardware and Fire Exit Hardware?
Resolution:
The most obvious difference (in the device) is the lack of mechanical dogging on a Fire Rated Device. There are some internal parts that may be different and the method it is secured to the d...:
What is an astragal?
Resolution:
An Astragal is an applied molding attached most commonly to the meeting edge of doors to: Protection against weather conditions Minimize the passage of light between the doors Retard the passa...: