inactive door leaf

RELATED FAQS

Question
Answer
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.
Ives SB360 surface bolt at top and bottom are the only flush bolts approved for use on H-Series hurricane FBC or NOA applications? The only approved latching hardware for inactive leaf of pairs w...
Astragal must be applied to pull side of active leaf, since placing the stragal on the inside of the inactive leaf will interfere with the active door closing.
Inactive Door, Wde Inactive
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts.  This may NOT be used on Fire Rated openings.
The backset for a 98/99 rim PANIC device with 1609 strike is 2 3/8" from center of the opening to center line of the device. See template
With a mullion: Use the standard strike 267 With no mullion and inactive leaf being held closed with flush or surface bolts: Use the 2609 double door strike
There are 2 types of door coordinators available: Bar Coordinators (Ives COR Series): Surface mounted to the bottom surface of the frame soffit. The active door lever, located nearest to th...
To determine Actual Door Size, the following values are subtracted from nominal door size (frame opening/order size) Actual Door Size: The largest measured width by height of the door leaf as m...