Steel transom panels are available: 1 3/4" thick panels - supplied in L-Series (L20, L18 or L16-Series) laminated construction. Recommended down sizing is as follows: Without Transom Bar 3...
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.  NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
Side Light and Side Panel frames - Side Light and Side Panel frames are not KD (Knock Down), they must be assembled and welded. All side lite and side panel frames must be assembled and welde...
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
The 4040 XP CUSH/EDA can be mounted on a Flush Transom frame by using a -419 Flush Panel adapter.
The 4110 series closer is installed on a flush transom frame using the -419 flush panel adapter.
An Astragal is an applied molding attached most commonly to the meeting edge of doors to: Protection against weather conditions Minimize the passage of light between the doors Retard the passa...
When using 98/9927 with flush transom above: You will need to use a 260U strike for flush transom applications OR a 260U-F strike for 98/9927-F fire rated device.