A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...
Dutch doors are available as Fire Rated door assemblies and have similar component requirements as a single leaf fire door. Exceptions are as follows: The Dutch Door assembly must have a lock...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed. Wire glass = 100 square inches is max exposed glass when wire glass is used. Note - ma...
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...
Steelcraft offers all the standard lights as well as special size glass lights in the H-series door. Effective April 1, 2012, (Bulletin # B-100.12) the default for Dezigner Trim in H-Series Doors...
You can only use one GBK Glass Bead Kit (1/4") per device on fire rated openings. Glass Bead Kit is for use on doors with raised glass beads.