electric strike solenoid burning up
”
RELATED FAQS
Question
Answer
What is the part number for the 6000 series electric strike 24VDC solenoid?
Resolution:
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below. Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 1...:
Are the Von Duprin 6000 series electric strikes rated for continuous duty?
Resolution:
All of Von Duprin 6000 series electric strikes have continuous duty solenoids either 12 or 24VDC.:
What is needed to keep the EL device retracted all day?
Resolution:
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...:
Can 24 volts be run to a 12 volt 6000 series electric strike solenoid?
Resolution:
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid. You must change to a 24V solenoid, part number 050240-00.: