Electric strike not locking

RELATED FAQS

Question
Answer
Follow the steps below to troubleshoot the problem. Measure the voltage at the electric strike. If the strike is FSE and not locking there should be no voltage at the strike and if it is FS there ...
The Von Duprin 6000 series electric strike has a 12 or 24VDC solenoid with plunger, spring and impact washer as shown 6000 solenoid Make sure the solenoid spring and impact washer are not missin...
The Von Duprin 6111 electric strike would work with DOM 1790 device on medium style doors Centerline of the 1790 device mounting screws are located 1 11/16" from face of stop. See d...
***The 6210 electric strike was designed to replace mechanical strikes in existing openings when access control is desired.*** Note: The Best 40H series lock is not listed on the 6210 electric s...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.  The XP device has 2000 pound holding forc...
 Von Duprin surface mounted 6300 electric strike paper template and installation instruction are provided with the electric strike. See attached 6300 Template & I...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
The wires on 6000 series electric strike solenoid are non polarized.
A Von Duprin 6111, 6112, or 6113 electric strike will work with a 1790 device.  The 6300 will not work.
The Von Duprin 2670 Guard X does not have a spring loaded latch bolt, it is a dead bolt and will not operate with any electric strikes.
The Von Duprin 5100 electric strike is not for fire rated applications.
Von Duprin doesn't offer any electric strike to fit into 1 1/2" aluminum/metal faced frame.  Minimum requirement to install 6211/6211AL is 1 15/32" mortise depth.
Von Duprin 6300 electric strike will operate with 88 rim but not 88F fire rated exit devices.
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
Electric strikes are not water proof an not recommended for exterior application especially gates.
No, due to the gate and backbox not being able to be sealed to keep water out of the electric strike a weather proof version is not available.
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...
There is not enough room to install two 6111 electric strikes back to back in 4854 mullion.
The Von Duprin 6210 electric strike was designed for retrofit applications and will not work with the Falcon MA series lock when strike and lock body are mounted at standard locations (centerline o...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike.
010055-xx is the part number for Blade Stop Shim kit for 6111 or 6113 electric strike and it must be ordered separately.  xx is for the finish callout.