electric strike NOT compatible with vertical rod devices

RELATED FAQS

Question
Answer
For non fire rated doors only the 1609 strike would be used on the inactive leaf that is flush/surface bolted or with a *surface or concealed vertical rod device on other door leaf.
To convert the Von Duprin 98/99 Rim or Vertical (Rod or Cable) Exit Device with functional lever (996L-R/V) to act like a rigid lever (996L-NL-R/V) with key over ride follow these steps: Remove ...
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
The AD or CO - 993 is NOT compatible with a Von Duprin 98/99 Concealed Vertical Rod exit device on wood doors.
The Von Duprin 6111 electric strike would work with DOM 1790 device on medium style doors Centerline of the 1790 device mounting screws are located 1 11/16" from face of stop. See d...
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
Yes, the current conversion kits will fit the old style/obsoleted 35 or 35 series vertical rod exit devices. 
***The 6210 electric strike was designed to replace mechanical strikes in existing openings when access control is desired.*** Note: The Best 40H series lock is not listed on the 6210 electric s...
The 98/99 rim and vertical rod exit devices are shipped with NL drive screw to function as a Night Latch. To convert the device to Class Room, remove the NL Drive Screw on 98/99 center case ass...