ELECTRIC HINGE LOCATION

RELATED FAQS

Question
Answer
"5, 10 and equal" Hinge Spacing: The industry terminology which usually refers to the Custom (NAAMM/HMMA) Door hinge locations. This location dictates: Top Hinge - located 5" from the underside ...
Cutout depends on the size of 224 hinge.  See 112HD/224HD-EPT template.  112HD/224HD continuous hinge  Center line of EPT to top of the door  83 inches  30 inches  85 inches  32 inc...
Fire labels (UL, ITS/WHI or FM) are located as follows: Butt Hinges and Pivots: On the doors the fire label is located on the hinge edge between the top and 2nd hinge preparation. On the fram...
From head to centerline of each hinge (4 1/2" or 5") is 9 3/4", 39 3/64", 68 11/32" & 97 41/64".
The hinge spacing on a 9'0" frame opening height is 29 19/64".
From Head to top of each 4 1/2" hinge is 7 1/2", 36 51/64", 66 3/32" & 95 25/64". From Head to top of each 5" hinge is 7 1/4", 36 35/64", 65 27/32" & 95 9/64".
Hinge Spacing: All 4 1/2" and 5" butt hinge spacing 1. Opening heights 3'0" through 4'11 15/16" (one pair butt hinges) from under head CL 9 3/4" (top of door 9 5/8") from bottom of frame ...
Hinge Backset: On the frame = 5/16" On the door = 1/4"
Lock Spacing: All standard bored locks ANSI 115.2 (161, 61L type), for mortise lock ANSI 115.1 (86 type) all locations must be altered 3/8" lower, and standard strike (ASA type). 1. Opening ...
The location to the top of hinge will vary depending on hinge size used. 6'8" Frame with 1 1/2 pair of hinges (top to top): For 4 1/2" hinges from the head to top of each hinge is 7 1/2", 37 7...
Steelcraft locates all butt hinges from the top of the door to the centerline of each hinge as standard practice: Locating hinges to the center line of the hinge keeps all hinge locations the sa...
The minimum top and bottom butt hinge locations are as follows: To the hinge centerline: 4 1/2" and 5" hinges = 5 3/8" is the minimum location from top of door to centerline of the first hi...
Using Soss hinges with closers can require special device and preparation locations. If you have questions on specific closer applications, please e-mail your request (including a description ...
EPT installation guidelines are as follows: Recommended location is 6" below top hinge per template Steelcraft will locate the power transfer prep at the Von Duprin recommended template locati...
Raceway availability: Optional factory installed raceways are available in doors but are not available in frames. Preparation Info: Steelcraft installs a flexible 1/2" ID steel conduit through the...
A raceway in a door provides a clear wiring access through the door core from hinge to lock edge. In a steel (hollow metal) door, the raceway is typically a length of conduit installed during d...
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
The Von Duprin 6111 electric strike would work with DOM 1790 device on medium style doors Centerline of the 1790 device mounting screws are located 1 11/16" from face of stop. See d...
 Von Duprin surface mounted 6300 electric strike paper template and installation instruction are provided with the electric strike. See attached 6300 Template & I...
No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.
The Schlage ES-6400 Electric Strike has been rebranded to Von Duprin 6400 Series Electric Strike, making Allegion’s full electric strike portfolio Von Duprin branded.  All product feature...
Information available at:  http://us.allegion.com/products/system_components/electric_strikes/pages/mortise_cylindrical.aspxOverview, Features and Benefits, Technical Specifications, Wiring In...
Cam Lift hinges can only be used with LCN door closers that have a "Regular" style arm.     Manual Closers: Maximum lift dimension is 3/4". Can not be use EDA, CUSH, or Track Arm do...
The Security Stud and TW4/8 (through wire) options are in the same location on a hinge and cannot be ordered together.
Swing clear hinges are available with TW (through wire).
The design change went into effect on 6-16-2011.  The stop is now removable and can be changed from one side of the shoe to the other, which makes it a non-handed arm.  All arms are shipped standar...
This engineering change did affect the templating of the closer. The stop in the shoe is slightly larger than the original handed cush shoe. The new non-handed arm template locates the closer and s...
Security anchors are used in DW/K frames located directly above or below strike preparation on door side of frame. Because there are only two points of anchoring, the compression anchor near the he...
Locate closer and arm from the centerline of the swing clear hinge pin.
The 4110 EDA/HEDA can be templated for 100°, 140°, and 180° hold open. The hold open adjustment can be set to hold the door at any position (degree) up to the maximum door opening angle. For "Wi...
For Steelcraft frame anchor locations refer to the frame "Anchoring Systems" section of Steelcraft's Tech Data Manual pages 2.4.1 thru 201.16.Basic guidelines are as follows:Anchor Quantities:• 3 p...
Reveal is the distance or measurement from the face of the door out to the face of the frame on the push side of the door.Other related terms:Door face - The exposed surface of door visible wh...
For both DW and K-Series Drywall Slip-on frames, Steelcraft locates the compression anchor in the jamb soffits approximately 4" down from the head on each jamb. Regardless of door opening height: ...
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required to turn&n...
It is recommended to use the Von Duprin EPT10 with CX device but if you need a door loop or electric hinge these are also acceptable. See attached table for wire run and gauge requirements: ...