el panic power supply

RELATED FAQS

Question
Answer
The 8200 can not supply the power needed on an EL dev ice. The EL device requires a Von Duprin PS914-2RS or PS914-4RL power supply or the older Von Duprin PS873-2 or PS873-4TD models.
The old MPB842 power supply will power up to two EL electric panic bars but will not power the QEL devices.  A defective potted module inside the electric panic bar or defective power supply coul...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
The 900-2RS option board is used with PS914 power supply to isolate the inputs such as key pads or card readers from the outputs for EL electric exit devices.  The EL draws 16 amp inrush that needs...
Reference The 914 Installation instructions.
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached ta...
Following could cause the fuse to blow in Von Duprin PS873 power supply. PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...