What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.:
How is a ELR or panic device wired to a Senior Swing?
Resolution:
EL devices are wired to the Senior Swing, using the P10 (761465) cable. Connect the "GRAY" wire to the SC terminal on the 900-2RS card in the Von Duprin Power Supply and the "VIOLET" wire to the ...:
Does the 4600 Series (4630 4640) operator have a built in relay?
Resolution:
Yes, the 4600 Series operators have a built in ES (electric strike) relay that can be used to unlock a strike, maglock, or EL device before opening the door.:
Can the 8200 Series operator power a electric strike?
Resolution:
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...: