delay egress length change

RELATED FAQS

Question
Answer
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field. The Chexit module would need to be replaced to reduce the release time of the Che...
One Deleay Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently
There is no conversion kit for Von Duprin Chexit device.  If delayed egress Chexit device is required, the entire device must be replaced.
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
Beginning with Firmware Packages ADFwPkg 2.16.3 and COFwPkg 1.20.0 the PIN length can be manually changed for AD200 and CO200 locks as follows: 1. Press {programming code (default is 97531)} then ...