cycle testing von duprin
”
RELATED FAQS
Question
Answer
What are cycle testing counts for exit devices?
Resolution:
ANSI grade one cycle test is 500,000, grade two is 250,000 and grade three is 100,000.:
What is the best way to test the Von Duprin EL solenoid?
Resolution:
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green...:
How do you test a Falcon 24 or 25 Series EL solenoid?
Resolution:
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...:
Does Von Duprin have a fire latch that will go into the floor?
Resolution:
Auxiliary fire latch is tested only from door to door latching by Von Duprin. Some door manufacturers have tested our devices LBR and use additional fire latches to pass the fire test. Contact the ...:
Why would the horn sound when the solenoid tries to engage on a Von Duprin Chexit device?
Resolution:
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...:
What would cause my 4600 (4630/4640) Series operator to keep trying to open and squeal after opening to 90 degrees?
Resolution:
"Opening Force" adjustment could be set to strong (high). This adjustment is a turn pot adjustment which can be found on the controller. Try adjusti...: