Crash bar with rex

RELATED FAQS

Question
Answer
This method is only available before the first network communication between an Access Control Panel (ACP) and the lock. Do a Level 1 and Level 2 Factory Default Reset (FDR) to remove any previ...
Manually Setting the RS-485 Address This method is only available before the first network communication between an Access Control Panel (ACP) and the lock. Do a Level 1 and Level 2 Factory De...
ALWAYS put the PIM400 in LINK mode first. On a PIM400-TD2 press the LINK1 Button for door one, and LINK2 button for door 2. With a PIM400-485 you must use the SUS/HHD to select which door to LINK.  
1. To put the AD400 in LINK mode, hold down the RTE (Lever or crash bar see below) and press the # key on the key board, or present a card to the reader.            Why press the # key? Because t...
2. AD400 requires a Request To Exit (RTX) signal to link - see the user guide instructions for the linking process.  For an AD400 to enter link mode, it must see the RTX (Request To Exit) switc...
   3. Check the AA battery level, if the AA batteries are below 4.7 volts the AD400 can fail to LINK.             Install fresh batteries, with a level of 6.0 volts or better.  
4. PIM400/AD400 COM400 plug could be damaged! The small pins in the Main PCB board connection for the RF COMM board can get bent during installation of the RF COM400 board. If the PINs are bent a...
Fire Device, Crashbar
Panic Device, Crashbar
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...