clearance fire rated
”
RELATED FAQS
Question
Answer
Can Steelcraft doors be prepped for the 98/9949 Concealed Vertical Cable Exit Device?
Resolution:
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device.L, B, CE, T and CE-Series doors are available factory preparedDoor prepa...:
Can a 3 hour A labeled Fire Door be prepped for multiple glass lights?
Resolution:
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...:
What are the different door cores available?
Resolution:
The five most common cores are honeycomb, polystyrene, polyurethane, steel stiffened, and temperature rise. Honeycomb core doors are used for interior and exterior openings where high thermal...:
What is the most common practice for running electric power from a frame to the door and hardware?
Resolution:
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into...:
Are masonry T anchor fire rated?
Resolution:
Masonry T anchor are approved for fire rated frames up to 3 hours. T Anchors are shipped lose for field installation. Anchor construction: The T portion and the strap do have minimum dim...:
What is the maximum door size for UL fire rated doors?
Resolution:
Maximum UL Fire Rated door sizes are as follows:A-Series:4' 0" X 8' 0" single door8' 0" X 8' 0” double door or pairsB-Series4' 0" X 10' 0" single door8' 0" X 10' 0” double door or pairsCE-Series:3'...:
Does wall board have to extend into the throat of a fire rated frame?
Resolution:
:
Can louvers be installed in fire rated transom frames?
Resolution:
NO - Louvers are not approved for installation in a fire rated transom / side panel frames. NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...:
Are Steelcraft doors and/or frames fire rated?
Resolution:
Yes, Steelcraft doors and/or frames are available and can carry a UL, WH or FM label. The type of fire label (UL, WH or FM) is dictated by the specifications and local building code. Doors ...:
What is an astragal?
Resolution:
An Astragal is an applied molding attached most commonly to the meeting edge of doors to: Protection against weather conditions Minimize the passage of light between the doors Retard the passa...:
Are astragals required on 3 hour rated pairs of doors?
Resolution:
All 3 hour fire rated pairs of doors do require an astragal when used without a removable hardware mullion. Pairs of doors with removable hardware mullions are treated and listed as 2 single doors...:
Does Steelcraft have frame installation instructions?
Resolution:
It is always recommended to point installers to the industry installation manuals which are very comprehensive and are ANSI documentsClick here to get the updated link to the Steelcraft Shop M...:
What astragals are available?
Resolution:
Types of astragal offered from Steelcraft are as follows: "Z" Astragal - For information on "Z" astragal types and attachment refer to the TD Manual page 3.3.17. Most commonly used on double ...:
What are the standard door and frame clearances?
Resolution:
To determine Actual Door Size, the following values are subtracted from nominal door size (frame opening/order size) Actual Door Size: The largest measured width by height of the door leaf as m...:
Where is the Fire Label located on a door and a frame?
Resolution:
Fire labels (UL, ITS/WHI or FM) are located as follows: Butt Hinges and Pivots: On the doors the fire label is located on the hinge edge between the top and 2nd hinge preparation. On the fram...:
Can a filler or cover plate be used to blank out a EPT prep on a fire rated frame?
Resolution:
Yes, a filler plate can be used to cover an EPT prep as long as it is made from the same material as the frame. This information can also be found in NFPA 80 under Chapter 5 for Field Modifications.:
What is the maximum size of a ITS/WHI fire rated three (3) sided frame?
Resolution:
ITS/WHI Fire Rated three (3) frames are available in the following maximum door opening sizes:F and FN-Series:4' 0" X 10' 0" single door8' 0" X 10' 0” double door or pairsMU-Series:4' 0" X 9' 0" si...:
What is ASTM E-119?
Resolution:
ASTM E-119 is a test standard for walls, partitions and floor or roof systems: This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames.As...:
Can wood doors be used with with double egress frames?
Resolution:
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames. Caution - For fire rated applications the wood door manufa...:
Can a 1 3/4" thick panel be used in a fire rated transom frame with a transom bar?
Resolution:
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...:
What is GrainTech?
Resolution:
GrainTech® is a Steelcraft door option which provides a wood grained pattern which is embossed into both face sheets of the door. GrainTech doors are factory stained and top coated with a cle...:
What fire ratings are available on DW-Series Borrowed Lights?
Resolution:
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...:
Can doors be prepared for raceways in the factory?
Resolution:
Raceway availability: Optional factory installed raceways are available in doors but are not available in frames. Preparation Info: Steelcraft installs a flexible 3/4" ID steel...:
Why are frames grouted?
Resolution:
Grouting frames is: A process done in the field during hollow metal frame installation The internal cavity of the frame is fill with masonry or mortar It is intended to mainly provide ...:
Can Von Duprin GBK's be stacked up to clear a 9/16" glass bead on a fire door?
Resolution:
You can only use one GBK Glass Bead Kit (1/4") per device on fire rated openings. Glass Bead Kit is for use on doors with raised glass beads.:
What is the maximum size of a UL fire rated three (3) sided frame?
Resolution:
Fire Rated three (3) frames are available in the following maximum door opening sizes: F and FN-Series frame:4' 0" X 10' 0" single door opening8' 0" X 10' 0” double door openingMU-Series frame...:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
What is the maximum glass light size on a 3 hour (180 minute) fire rated door?
Resolution:
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...:
What is the maximum glass light size on a 90 min (1 1/2 hour) fire rated door?
Resolution:
Standard listed wire glass: one (1) light with 100 in2 per door leaf max.Firelite or other appropriately listed glass:• FM maintains one (1) light with 100 in2 per door leaf max.• UL &...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
What is the largest diameter hole that Steelcraft can provide for viewer preps?
Resolution:
Non fire rated doors can be furnished with a maximum 3" diameter hole for viewer preparations.Fire rated doors have a 3/4" maximum holes size unless otherwise listed by UL or ITS/WHI. Viewers must ...:
Are hospital stops approved on fire rated frames?
Resolution:
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes: singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...:
What is the max rating available on an full glass (FG) door?
Resolution:
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...:
What is a U-Factor?
Resolution:
The U-Factor, R-Value and K-Thermal Rating are measurements of thermal transmission through building products. U-Factor: Overall co-efficient of heat transmission passage through a built-up panel...:
Are frames available without backbends?
Resolution:
F-Series frames are available without returns: Fire Rated frames must have welded corners. Frames must include weled in wood or steel stud anchors. Installation requirements: ...:
Is GrainTech available fire rated?
Resolution:
GrainTech® is available with very broad fire ratings.The option of GrainTech® does not affect the fire rating of the door.Fire ratings depend on the door series, hardware and applications.For all f...:
Are thermal break frames available?
Resolution:
Additional information on Thermal Break Frames can be found on Tech Data Pages 224 thru 227 :
What are the maximum door width and height sizes?
Resolution:
Maximum nominal (overall) single door sizes are as follows:L-Series (Laminated Door)20 Gage = 3’ 0” wide X 8’ 0” high18 Gage = 4’ 0” wide X 10’ 0” high16 Gage = 4’ 0” wide X 10’ 0” high1...:
Are doors available for use with non Steelcraft window kits?
Resolution:
Doors are available with cutouts only. This practice is used for field installation of aftermarket (non-Steelcraft) glass trim by either the distributor or end user. The following information must ...:
Are GrainTech doors available with hardware preps?
Resolution:
All hardware options (available on standard door) are available on GrainTech® doors. Available hardware are covered in the Steelcraft Price Manual. GrainTech® doors can be prepped for the Von Dupr...:
What is a communicating frame?
Resolution:
Communicating Frames are hollow metal frame fabricated such that a door is installed in each rabbet of a double rabbeted frame (2 doors total) to facilitate dual access and control of the opening, ...:
What glass light kits are available in doors?
Resolution:
Glass Light is a preparation in a door for view window, vision and/or glazing including glass stop and glazing bead and may also be refereed to as a lite.Doors are available with a wide v...:
What is the maximum frame size for a label transom and sidelight frame?
Resolution:
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes).In masonry wall application the maximum is 13'6" x 12'2"In stud wall application the maxi...:
Is a 20 minute label door a real fire door?
Resolution:
The 20 minute Fire Rating is a valid label and are commonly referred to as "Smoke and Draft control door assemblies". Depending on the local fire code and the openings's applica...:
Can decorative metal panels be installed over the entire surface of fire doors?
Resolution:
Decorative metal panels can only be attached if the panel manufacturer is UL listed in UL’s category GVUZ. All installation, sizes and hourly ratings are in accordance with that manufacturers” ...:
What Steelcraft doors can be prepped for a Von Duprin InPact device?
Resolution:
Steelcraft L-Series and T-Series doors are available (as an option) factory prepared for the Von Duprin InPact exit device. :
What is the maximum door size for ITS/WHI fire rated doors?
Resolution:
ITS/WHI is "Warnoch Hersey". ITS/WHI is the formal designation for Intertek Testing Services / Warnock Hersey. ITS/WHI is an independent agency with testing, listing, in-plant inspection, and label...:
What frame profile variations are available on fire rated transom sidelights and window?
Resolution:
Elevation frames are available in: F-Series (F16 or F14) FN-Series (FN16 or FN14) MU-Series (MU16, MU14) Additional parameters of the frame components: Perimeter (Head and Jambs) Frame: ...:
Are intumescent seals or gaskets required on fire rated steel doors?
Resolution:
Intumescent seals or gaskets are not required on fire rated steel doors. Generally speaking, the requirement for intumescent seals or gaskets are a function of the individual manufacturers’ listi...:
Can an additional jamb anchor be used as a base anchor on fire rated frames?
Resolution:
Yes, an additional jamb anchor can be used at the bottom of the frame in lieu of the typical (adjustable or weld-in) base anchor in fire rated frames. This is limited to the anchor designed for...:
Can fire rated double egress frames have side lights or transoms?
Resolution:
No. Fire rated double egress frames must be a stand alone 3 sided frame assembly. If transom lights and/or sidelights are required, they must be built and installed as separate Fire Window assemb...:
Are FM fire rated door and frame products available?
Resolution:
FM Global is an independent underwriting agency with listing, in-plant inspection, and labeling capabilities.FM fire rated doors and frames are available, however there are a minimal amount of...:
How many P & D (Pierce and Dimple) holes are in a frame?
Resolution:
The following are quantities of EMA anchors (pierce and dimples) based on range of frame height: Quantity Nominal Frame Height 2 1'...: