chexit flashes once when armed, no alarm, free egress
”
RELATED FAQS
Question
Answer
What would cause the Von Duprin Chexit device to have one red flash when armed then nothing?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...:
Von Duprin Chexit device keeps going into alarm by itself.
Resolution:
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
Why does my Chexit device open without sounding the alarm?
Resolution:
: