chexit fire wiring

RELATED FAQS

Question
Answer
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
The EL Wiring Adapter is not needed for a CX device.
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
Chexit devices shipped after 8-24-2015 with motor driven has a twelve wire connector wires and is keyed and can only plugged into the Chexit module in one direction.Chexit devices shipped...
The part number for "CX Wiring Assembly" also called "Ten Wire Connector" is 112018-00.
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...