chexit device minimum door

RELATED FAQS

Question
Answer
Chexit devices are NOT electric latch retraction.  In order for Chexit device to operate with an auto operator you will need to add a rim electric strike on a single door or a pair o...
A Door Position Switch is a switch and magnet mounted on the door and frame that monitors the door status. If door is held open beyond rearm time or if door is forced open, alarm wil...
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
Minimum door opening on double door with 98/9927 should be 25.5" and single door is 25.65".
For most exit devices, please refer to the specific device series catalog for minimum door opening width the device can be cut down to fit.Be aware that some device options, frame conditions, and s...
The Minimum single door opening should be 26.32" and use the 299 or 499F strike.
55 and 88 are both crossbar exit devices.  55 Series is used on narrow stile applications, 88 is for wider stile applications. See attached tables for 55 and 88 series minimum stile requirement...
The Von Duprin CX 98/99-4 feet Rim devices on single doors with 5/8" stops and the standard 299 roller strike can be field sized to fit a minimum of 40.2" door opening.  This an...