can RATED DOUBLE EGRESS OPENING have hospital stops

RELATED FAQS

Question
Answer
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes:  singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...
Hospital Stops are located at the bottom of the frame jambs and/or mullions. The integral door stops are terminates above floor line and is closed with a 45° or 90° angle to facilitate cleaning at ...
Hospital Stops are available as either: 45° Hospital Stop - the stop of the frame terminates at a 45° angle 90° Hospital Stop - the stop of the frame terminates at a 90° angle The type of hos...
Types of astragal offered from Steelcraft are as follows: "Z" Astragal - For information on "Z" astragal types and attachment refer to the TD Manual page 3.3.17. Most commonly used on double ...
The rough opening dimensions are the same for either Welded (SUA) or Knock Down (KD) frames For F, FN, FE, DE, MU three sided frames and four sided borrowed light frames: New masonry Walls: N...
 For DW, K three sided frames and four sided borrowed light frames: Three sided frame = door opening width (order size) plus 1 1/2" minimum to 2" maximum and the door opening height ...
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames. Caution - For fire rated applications the wood door manufa...
No. Fire rated double egress frames must be a stand alone 3 sided frame assembly. If transom lights and/or sidelights are required, they must be built and installed as separate Fire Window assemb...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...