can i use less bottom rod

RELATED FAQS

Question
Answer
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
This is available. If this is a fire rated opening you must use the Auxiliary Fire Latch Kit to maintain your Fire Rating.  If not fire rated simply omit the bottom rod but be aware that your...
The Von Duprin 2227 or 2227-F  exit device is available less bottom rod.  Specify 2227-LBR or 2227F-LBR for fire.
The 8827L-LBR panic only, not fire rated can be ordered LBR.
The 8827 cannot be ordered Less Bottom Rod, but can be installed without the bottom rod.  The device was never tested without the bottom rod, that is why it cannot be ordered LBR.
Von Duprin will not supply the 8827-F less the bottom rod because the device has never been UL tested less bottom rod.
Installation should be 6" from bottom of the door. See attached templates as reference.  T-5494 for HM Doors W-5494 for Wood Doors
The Von Duprin 5547/WDC/F has never been tested with less bottom rod through UL and is only sold with both top and bottom rods.  You may choose not to install the bottom rod on non fire rated devic...