benchmark hold open switch

RELATED FAQS

Question
Answer
If the 9100 Series Benchmark operator does not open when the actuator is pushed: Verify the unit has 120 volts applied to it. Verify the the power light on the control box is on. If not, check ...
The 4040 regular and hold open arms are different. You would have to get a different arm to convert from regular arm to a hold open function. 4040-3077 for a regular arm. 4040-3077L for a long ...
The Benchmark and Falcon operator gearbox assemblies are not repairable. The gearbox belt and/or pulley cannot be replaced in the field, the gearbox would need to be replaced as a complete assembly...
The ES Filter started to ship with these units (Senior Swing/Benchmark/Falcon) on 4/22/2013.  The ES Filter kit will help eliminate line noise from an Electric Strike if used. 
On the Senior Swing, if you have line noise from a strike the unit will go into an Error Code on the Control Box (Er14) and will not operate.  Adding the ES Filter, which is a diode, will eliminate...
On the Benchmark and Falcon, if there is line noise from a strike then the unit will lose it's hold open time.  Adding the ES Filter, which is a diode, will resolve this issue and the unit will hol...
The 4600 hold open switch (for the new 1-24 single terminal strip I/O board) wires into terminals 2 and 6 or 4 and 6.
The 4610/4620 series operators are obsolete. There is no replacement part for any electronic component (motor/clutch, controller, input/output PC boards) for the obsolete 4610/4620 operators.Essent...
The Senior Swing has an optional (plug in) Off/Auto/Hold Open switch available. The 8310-806R (rocker switch), or 8310-806K (key switch). CANNOT use switch by others, requires a special (center - n...
The 8310-806K/R is used when a remote OFF/AUTO/HOLD OPEN is required and is normally used with a 4630/4640 CS (concealed switch) unit.
For wiring diagram see here.