auto rearm on ALK
”
RELATED FAQS
Question
Answer
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...:
Alk not power up - using 9V battery
Resolution:
There are three main failures with an ALK. Problems are usually caused by a bad power source(battery), bad RX/LX Switch or a bad circuit board. Try installing a new battery and wai...:
Will the PT790 work with the ALK?
Resolution:
The new exit alarm ALK uses the 24VDC regulated PS902 power supply.: