ADA closers opening force for exterior doors
”
RELATED FAQS
Question
Answer
Do Von Duprin Exit devices meet the 5 pound force requirement for opening an ADA handicapped door opening?
Resolution:
The 5 pound force requirement is in reference to the maximum force to swing the door, not the maximum force allowed to unlatch the exit device. Maximum allowed force to retract the Von D...:
What is the minimum clear opening width required by ADA on a single door?
Resolution:
The minimum clear opening width for ADA is 32" measured from face of door opened to 90 degrees to face of stop on strike jamb. There must be no hardware mounted to the door projectin...:
Can you manually pull a 4040SE out of hold open?
Resolution:
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force. :
How do you adjust a door closer?
Resolution:
How to: What are the steps to adjust a door closer? Facts: All LCN and FALCON door closers will have 3 regulating valves and a spring adjustment. All cl...:
Can I get a Senior Swing with a reduced opening force gearbox?
Resolution:
The older model Senior Swing came with 2 spring options. The "standard force" spring required 15 lbs of manual opening force, and reduced force "RF" required 11 lbs of manual opening force. All S...:
Why would a 4600 not open a full 90 degrees?
Resolution:
A 4600 (4630/4640) not opening to a full 90 degrees could be caused by a couple things: The Opening Force could be set too low. Try increasing the opening force adjustment on the controller a 1/...:
Are the Falcon SC Series door closers fire rated?
Resolution:
Yes, the Falcon SC Series closers have a UL listing.: