Will the 9550 series Senior Swing work with a strike and auto flush bolts?

The 9550 series Senior Swing WILL NOT work on a pair of doors with Electric Strike and auto flush bolts because you cannot sequence the door openings with a 9550 simultaneous pair operator.  

To sequence the opening of the door leaves you will need the 9560 series independent pair Senior Swing PLUS a separate sequencing module such as the LCN 8310-845 relay and door sequencer (set to function 65).  See here for 8310-845 relay and door sequencer instructions/programming.

When programming the 8310-845 (function 65) for auto flush bolts set the parameters to the following.

  • h1 = 01
  • h2 = 01
  • d1 = 02
  • d2 = 00

In the case of a Fire Rated opening, a Coordinator will be required to ensure the doors can properly close and latch in the event of power loss.

For a general LCN example wiring diagram see here.