The AD Series wireless family of products are NOT UL plenum rated.
Because the AD Series wireless products contain a 900 MHz radio, they cannot be in a metal box or obstructed by metal like ceiling grid framing, duct work, pipes or conduit.
The AD Series offline CT5000 controller is NOT UL plenum rated
Because the AD Series offline CT5000 is housed in a plastic enclosure, it does not pass the Plenum, requirement
The AD Series online PIB-300 is NOT UL plenum rated
Because the AD Series online PIB-300 is housed in a plastic enclosure, it does not pass the Plenum, requirement
Plenum rating requires UL 2043 approval,
The AD Series wirless products were not tested to the plenum UL 2043 requirements because their plastic box enclosure(s), will fail the Plenum evaluation
The AD Series WPR-400 and WRI-400 and PIM400-1501 versions are not Plenum rated
INFORMATION PROVIDED THROUGH THIS SITE IS PROVIDED TO YOU AS IS WITHOUT ANY EXPRESS REPRESENTATIONS OR WARRANTIES OF ANY KIND, AND WE MAKE NO REPRESENTATION OR WARRANTY THAT THIS SITE(OR ANY INFORMATION PROVIDED IN RESPONSE TO YOUR INQUIRY), WILL BE ACCURATE, COMPLETE, OR ERROR-FREE.
YOU AGREE THAT YOU MUST EVALUATE ALL INFORMATION AND RESPONSES, AND THAT YOU BEAR ALL RISKS ASSOCIATED WITH, THE USE OF THIS SITE, INCLUDING ANY RELIANCE ON THE ACCURACY,COMPLETENESS, OR USEFULNESS OF ANY INFORMATION OR MATERIALS MADE AVAILABLE THROUGH THIS SITE.